设备安装参考数据p620-6F1
7025 Deskside 6F1 Series
Dimensions
Height 610 mm 24.0 in.
Width 483 mm 19.0 in.
Depth 728 mm 28.7 in.
Weight
Minimum configuration 70 kg 155 lbs.
Maximum configuration 95 kg 209 lbs.
Electrical
Power source loading typical in kVA 0.59
Power source loading maximum in kVA 0.86
Voltage range (V ac) 100 to 127 or 200 to 240 (autoranging)
Frequency (hertz) 50 or 60
Thermal output (typical) 1920 Btu/hr
Thermal output (maximum) 2867 Btu/hr
Power requirements (typical) 560 watts
Power requirements (maximum) 840 watts
Power factor 0.95
Inrush current3 70 amps
Maximum altitude. 2135 m (7000 ft.)
Temperature Requirements Operating.
10 to 38亱C
(50 to 100亱F)
Non-Operating
10 to 43亱C
(50 to 110亱F)
Humidity Requirements Operating. Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 23亱C (73亱F) 27亱C (80亱F)
Noise Emissions1 Operating Idle
LWAd 6.1 bels 5.9 bels
LpAm N/A N/A
Impulsive or prominent discrete tones No No
Clearances Front Back Left Right
Install/Air Flow2 76mm(3 in) 152mm(6 in) 51mm(2 in) 51mm(2 in)
Service Install so that it can be moved to an area providing 457 mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Footprint2 Width
585mm(23 in)
Depth
956mm(37.7 in)
1. See 乬Noise Emission Notes乭 on page 199 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. A)Dry bulb temperature derating at high altitude: Upper limit temperature must be derated 1.0 deg C per 137 m
of elevation beyond 1295 m above sea level. (1 deg F per 250 ft above 4250 feet). B) Wet bulb temperature
derating at high altitude: Upper limit temperature must be derated 1 deg C per 274 m of elevation beyond 1372m
above sea level (1 deg F per 500 ft above 4500 feet).