Wire Sizing and Ampacities Charts
12 Volt 2% Wire Loss Chart
Maximum distance one-way in feet of various gauge two conductor copper wire from power source to load for 2% voltage drop in a 12 volt system. You can go twice the distance where a 4% loss is acceptable. Do not exceed the 2% drop for wire between PV modules and batteries. A 4 to 5% loss is acceptable between batteries and lighting circuits in most cases. Multiply distances by 2 for 24 volts and by 4 for 48 volts.
2% Voltage Drop Chart | ||||||||||
Amps | #14 | #12 | #10 | #8 | #6 | #4 | #2 | #1/0 | #2/0 | #4/0 |
1 | 45 | 70 | 115 | 180 | 290 | 456 | 720 | . | . | . |
2 | 22.5 | 35 | 57.5 | 90 | 145 | 228 | 360 | 580 | 720 | 1060 |
4 | 10 | 17.5 | 27.5 | 45 | 72.5 | 114 | 180 | 290 | 360 | 580 |
6 | 7.5 | 12 | 17.5 | 30 | 47.5 | 75 | 120 | 193 | 243 | 380 |
8 | 5.5 | 8.5 | 11.5 | 22.5 | 35.5 | 57 | 90 | 145 | 180 | 290 |
10 | 4.5 | 7 | 11.5 | 18 | 28.5 | 45.5 | 72.5 | 115 | 145 | 230 |
15 | 3 | 4.5 | 7 | 12 | 19 | 30 | 48 | 76.5 | 96 | 150 |
20 | 2 | 3.5 | 5.5 | 9 | 14.5 | 22.5 | 36 | 57.5 | 72.5 | 116 |
25 | 1.8 | 2.8 | 4.5 | 7 | 11.5 | 18 | 29 | 46 | 58 | 92 |
30 | 1.5 | 2.4 | 3.5 | 6 | 9.5 | 15 | 24 | 38.5 | 48.5 | 77 |
40 | . | . | 2.8 | 4.5 | 7 | 11.5 | 18 | 29 | 36 | 56 |
50 | . | . | 2.3 | 3.6 | 5.5 | 9 | 14.5 | 23 | 29 | 46 |
100 | . | . | . | . | 2.9 | 4.6 | 7.2 | 11.5 | 14.5 | 23 |
150 | . | . | . | . | . | . | 4.8 | 7.7 | 9.7 | 15 |
200 | . | . | . | . | . | . | 3.6 | 5.8 | 7.3 | 11 |
Maximum Ampacities for Wire
Allowable ampacities of conductors (wires) in conduit, raceway, cable or directly buried, based on ambient temperature of 86